KNX Secure btn I/F 4-g Komfort [519400] Button interface, 4-gang Komfort for KNX Gira operating devices for KNX Merkmale: - According to the variant, two, four or eight independent channels that operate as inputs or as outputs depending on the ETS parameterisation. - Common reference potential for all channels. - Outputs: Connection of LED. Short-circuit-proof, protected against overload and polarity reversal. Parallel switching of outputs possible, for consumers with higher current requirements - Inputs: Pulse current to prevent contact contamination due to formation of an oxide layer on the connected contacts. - Channels can be activated and deactivated individually. - Adjacent activated channels can be combined. Possible parameterisation depending on the selected channel function - Contact type can be set. - Switching: Command when pressed and/or released can be set (No reaction; Switch on; Switch off; Switch over). - Forced setting: Command when pressed and/or released can be set (No reaction; Forced active, Switch on; Forced active, Switch off; Forced inactive). - Dimming and colour temperature: The command when pressed, time between switching and dimming, dimming in different steps, telegram repetition if pressed for a long time and sending of a stop telegram at the end of pressing can be set. - Blind/shutter/awning/roof window: Command when pressed and command sequence can be set. - Value transmitter: Data point type, value range and value can be set. As an option, the value adjustment can be activated by pressing and holding the button. - Scene auxiliary unit: Scene number can be retrieved or switched by briefly pressing the button. If the button is pressed and held, the memory function is executed as an option. - Short and long button press: Up to two telegrams can be sent to the KNX by pressing a button. The transmission behaviour can be set and the time for short and long actuation can be adjusted. The mode of operation of the channels can be set separately. - Room temperature controller operating point: The mode of operation (operating mode switch-over, forced operating mode switch-over, presence function and target temperature adjustment) can be set. - Behaviour after bus voltage recovery can be set. - Disable function can be set. - Cyclic transmission can be set. - Channel function “Door/window status”: When door or window contacts are used, the different window or door statuses can be evaluated (open, closed, tilted, locked, unlocked). - Evaluation of a leakage/condensation sensor. - Temperature measurement by connected sensor possible. - Temperature measurement can be supplemented by external value via bus. Measured values can be weighted and calibrated. Pulse meter - Metering interval can be set. - Number of pulses required at the input per reported meter pulse can be parameterised on the KNX. - The number of meter pulses required for a meter status change can be parameterised. - Each channel contains a main meter and an intermediate meter. - Main and intermediate meters can be set separately as up or down meters. - Start and end values of the meters can be specified via parameters or communication objects. - Meter status can be queried via the KNX or transmitted automatically. - Response after the meter has timed out can be parameterised. - The pulse meter can be reset via the KNX (meter reset). Logic functions - The device has 8 internal logic functions. - Invert input. - Logic gate with up to 4 inputs: AND, OR, exclusive OR, inverted AND, inverted OR, inverted exclusive OR, AND with return. - 1-bit to 1-byte converter with input filter, blocking object and specification of output values. - Blocking element with filter and time functions and blocking object. - Comparator for values with 9 different input data formats and many comparison operations. - Limit value switch with hysteresis with upper and lower threshold values for 9 different input data formats. Including specification of the 1-bit output values. - The logic functions have their own KNX communication objects and can process telegrams from the button interface or other bus devices. Technische Daten: KNX medium: TP256 Output voltage: max. 3.2 mA LED current: 2.2 mA per output Length cable set: 25 cm, can be extended to max. 30 m Protection class: IP20 Ambient temperature: -5 °C to +45 °C Number of inputs: 4 Dimensions (LxWxH): 43.0 x 28.5 x 15.4 mm Current consumption: 5 to 12 mA Connection: Connection and junction terminal Input cable: 5-wire cable set Hinweise: - KNX Data Secure compatible. - Firmware can be updated using the Gira ETS Service App (additional software). Lieferumfang: - Connection and junction terminal - 5-wire cable set Fabrikat: Gira Bestell-Nr. 5194 00 Menge: 0 Stk xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx