KNX DRA pow.supply 160 mA choke [212000] Power supply 160 mA with integrated choke for KNX Gira system devices, actuators,sensors, accessories for KNX DRA Merkmale: - Output with integrated choke to supply KNX bus lines. - Output DC 30 V to supply additional devices. - Rated current can be flexibly split up amongst outputs. - Reset button. - Short-circuit-proof. - Overvoltage protection. - Open circuit-proof. - Suitable for operation in systems with emergency power supply. - Isolated signal contact for operating message and diagnostic message. - Two power supplies for KNX of the same type for can be connected directly in parallel to increase power. Technische Daten: Rated voltage - AC: AC 200 to 240 V, 50/60 Hz - DC: DC 240 to 250 V Output voltage - KNX line: DC 28 to 31 V SELV - Additional output: DC 30 V Signal output - AC switching voltage: AC 12 to 230 V - Switching voltage DC: DC 2 to 30 V - Switching current: 5 mA to 2 A Connections - KNX: Connection and junction terminal - Mains voltage: Screw terminals Connection cross section: Max. 4 mm² Ambient temperature: -5 °C to +45 °C Output current: 160 mA Short-circuit current: max. 1 A Hinweise: - Installation on DIN top-hat rail. - VDE approval in accordance with EN 60669-1, EN 60669-2-1. Lieferumfang: - Connection and junction terminal for KNX included with delivery. Abmessungen: Teilungseinheiten (TE): 4 Fabrikat: Gira Bestell-Nr. 2120 00 DRA Menge: 0 Stk Einzelpreis: 151.33 Euro (o. MwSt.) xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx